House Thermography Reference logo — a house outline shaded from cold to warmHouse Thermography ReferenceWhat an infrared image of a house shows, and what it cannot
Line illustration of a pressure gauge with an inspection tag hung from it representing A Hot Breaker or Connection
Moisture and building systemsElectrical and mechanicalNeeds confirming

A Hot Breaker or Connection

A connection running hotter than its neighbors is one of the most useful things a thermal camera can find. It is also the reading most dependent on how much current was flowing when the image was taken.

What the pattern looks like

With the dead front (the inner cover) of a panel removed, a thermal image shows breakers, bus connections, lugs and wire terminations. Under load, conductors and breakers run warm, and breakers carrying similar current should look similar. A finding stands out as one breaker, one terminal screw or one lug distinctly hotter than the others, often with heat spreading along the wire from the hot point.

With the dead front on, only the surface of the cover is visible, and a hot spot shows only as a faint warm area on the metal or plastic, if at all.

Why it matters

Heat at a connection usually means resistance, and resistance usually means a loose, corroded or damaged connection, or a component carrying more current than it should. HUD's research office, in its overview of thermal imaging for building diagnostics, notes that overheated outlets can indicate overloaded circuits, damage or loose wiring. The same logic applies inside the panel. A connection that heats can get worse over time.

How the industry ranks temperature rise

The criteria most commonly cited in North America are in Table 100.18 of the ANSI/NETA testing specifications, published by the InterNational Electrical Testing Association for commercial and industrial equipment. As reported by Fluke and others, when comparing similar components under similar loading, a temperature rise of 1 to 3 °C indicates a possible deficiency that warrants investigation, 4 to 15 °C a probable deficiency to repair as time permits, and more than 15 °C a major discrepancy to repair immediately. A separate column compares components with ambient air.

Those thresholds were written for facility electrical maintenance, by qualified electrical testers, with known loads. They are useful as a sense of scale in a house. They are not a rule a home inspector applies.

NFPA 70B, the standard for electrical equipment maintenance, became a mandatory standard rather than a recommended practice in its 2023 edition. As reported by Teledyne FLIR and TÜV SÜD, it calls for thermographic inspection of electrical equipment in a maintenance program at least every 12 months, and every 6 months for equipment in poor condition. That is facility practice. No comparable requirement applies to houses.

Why load decides what you see

A breaker serving a circuit that is off, or carrying a few amps, produces little heat even if its connection is poor. A panel scanned in the middle of a mild afternoon with nothing running can look perfectly even and still have a bad connection. Electrical thermographers in facilities record the load and try to scan at a substantial share of normal load. In a house, running the dryer, the range, the water heater or a space heater before the scan makes those circuits visible.

What New Hampshire inspectors may and may not do

New Hampshire's home inspection standards of practice require the inspector to inspect the interior components of service panels and subpanels, and to report the reason if a panel cover could not be removed. Home 603.02(w) also says the home inspector shall not measure amperage, voltage or impedance. The standards do not mention thermal imaging. An inspector who scans a panel is going beyond the minimum, and the image is a reason to call an electrician, not a diagnosis. The guide to New Hampshire home inspections and infrared covers the scope.

What else produces a similar pattern

Normal load. A breaker carrying a heavy load runs warmer than lightly loaded neighbors for a sound reason. The comparison has to be like with like.

Reflections. Bare copper, aluminum and polished bus bars have low emissivity and reflect the surroundings. See emissivity and reflections.

Electronic breakers. Arc-fault and ground-fault breakers contain electronics and run slightly warm by design.

Common mistakes

Reading a cold panel as a clean panel. No load, no heat.

Taking the temperature as exact. Shiny metal makes the number unreliable; the pattern matters more than the figure.

Opening a panel without training. Removing a dead front exposes energized parts. Electrical thermography in facilities is done under electrical safety rules for that reason.

What to do with it

Any connection that reads markedly hotter than similar parts under similar load is a call for a licensed electrician, who can check torque, look for damage and measure current. Ask for the image, the load at the time and the temperature difference. A warm outlet or switch found on the same survey belongs in the same conversation.

Where the guidance comes from

The New Hampshire standards are in the Home 100-700 rules. Fluke describes the NETA criteria in Using thermal imaging cameras for electrical inspections. Teledyne FLIR summarizes the 2023 NFPA 70B changes in NFPA 70B 2023: New Guidelines for Electric Inspections.

Frequently Asked Questions

Is a warm breaker dangerous?

Breakers carrying current are normally warm. A breaker or connection much hotter than similar parts under similar load needs an electrician's attention.

Why did the panel look normal on the thermal image?

Probably because little current was flowing. Heat at a bad connection depends on load.

Do New Hampshire home inspectors test electrical loads?

No. The standards of practice say the inspector shall not measure amperage, voltage or impedance.

Does NFPA 70B apply to my house?

NFPA 70B governs electrical maintenance programs, which are a facility practice. It does not set requirements for single-family homes.