House Thermography Reference logo — a house outline shaded from cold to warmHouse Thermography ReferenceWhat an infrared image of a house shows, and what it cannot
How thermal imaging works

Emissivity and reflections: why a thermal camera can misread shiny surfaces

A thermal camera reads the infrared a surface gives off, plus whatever that surface reflects. On paint and drywall the reading is honest. On shiny metal, glass and foil it often is not.

The short answer

Every surface gives off infrared energy according to its temperature and its emissivity, a number from 0 to 1 describing how efficiently it radiates compared with a perfect emitter. Most building surfaces, such as paint, drywall, wood, brick and concrete, have high emissivity, around 0.9, and a thermal camera reads them well. Polished metals, foil, and many glazed and coated surfaces have low emissivity. They give off little of their own infrared and reflect a lot of their surroundings, so the camera sees a mixture of the surface and its reflection. That is the most common source of false readings in building thermography.

What emissivity is

Teledyne FLIR describes emissivity as how well a surface "tells the truth" about its temperature. A surface with emissivity of 1 radiates all the energy its temperature allows. A surface with emissivity of 0.1 radiates a tenth of that and, if it is opaque, reflects the other nine tenths of what falls on it from its surroundings.

FLIR gives typical figures: highly polished metals such as copper or aluminum usually below 0.10; roughened or oxidized metals 0.6 or higher depending on the surface; most flat paints around 0.90; skin and water about 0.98. Fluke's published table lists polished aluminum at 0.05, oil paint at 0.94, concrete at 0.92 and black electrical tape at 0.95.

Why it matters in a house

Building interiors are mostly high-emissivity surfaces, which is why thermal imaging works as well as it does indoors. The trouble is concentrated in a few places:

  • Electrical panels. Bus bars, lugs and bare copper are shiny. A bad connection on a shiny lug can read cooler than it is. See a hot breaker or connection.
  • Pipes. Bare copper water and heating pipes read low and reflect the room. Painted pipe reads well. See hydronic baseboard and heating pipes.
  • Ducts and foil. Foil-faced duct wrap, foil tape and radiant barriers reflect strongly. See duct leaks and disconnected ducts.
  • Glass. Glass is close to opaque to the long-wave infrared building cameras use, so the camera sees the glass surface, not what is behind it, and the glass reflects. See air leakage at windows and doors.
  • Metal trim and plates. Chrome cover plates, appliance fronts, flashing and metal roofing all mislead.

Reflections, the practical problem

The camera's temperature reading assumes an emissivity, set by the operator or left at a default. On a low-emissivity surface, the reading depends heavily on the reflected temperature (the temperature of whatever is being reflected), which FLIR describes as thermal radiation from other objects reflecting off the target. A shiny panel cover can show a "hot spot" that is the thermographer's own body. A window at night can reflect the cold sky. A metal roof can show bright patches that are reflections of the sun or nearby warm surfaces.

How thermographers check

Move. Change the viewing angle and look again. A reflection moves with the camera; a real temperature pattern stays in place on the surface.

Compare with a known surface. A piece of electrical tape or a dab of flat paint on a metal surface creates a spot with known high emissivity. After a few minutes it reaches the surface temperature and can be read reliably.

Set the parameters. Good practice is to set emissivity and reflected temperature for the surface being measured. For qualitative building work, where the question is "is this area different from that one", consistency matters more than an exact number.

Prefer patterns to numbers. On low-emissivity surfaces, trust the shape and the comparison more than the figure.

What this means for a report

When a thermal image in a report carries a temperature reading, ask what surface it was taken on. A reading on painted drywall is credible. A reading on a bare lug, a copper pipe or foil tape is an estimate unless the report says how emissivity was handled. Reports that use temperature numbers to rank electrical findings should say so.

Common mistakes

Trusting the default. Many cameras default to an emissivity around 0.95, fine for drywall, wrong for bare metal.

Imaging glass to see inside. It does not work.

Reporting reflections. A hot spot that follows the camera around a room is the operator.

Where the guidance comes from

Teledyne FLIR, How does emissivity affect thermal imaging?, and Fluke's published table of emissivity values for common materials. The broader framework for building thermography, including the qualifications of operators and analysts, is set out in ISO 6781-1:2023.

Frequently Asked Questions

What is emissivity?

A number from 0 to 1 describing how efficiently a surface radiates infrared compared with a perfect emitter. Paint is around 0.9; polished aluminum is around 0.05.

Why does shiny metal read the wrong temperature?

It radiates little of its own infrared and reflects its surroundings, so the camera reads a mixture of the surface and its reflection.

Can a thermal camera see through glass?

Not ordinary window glass. Building cameras see the glass surface, which also reflects infrared.

How do thermographers measure a shiny surface?

They add a high-emissivity patch, such as electrical tape or flat paint, and read that, or they compare patterns rather than rely on the number.