House Thermography Reference logo — a house outline shaded from cold to warmHouse Thermography ReferenceWhat an infrared image of a house shows, and what it cannot
Infrared in a home inspection

The standards behind building thermography: ASTM, ISO, NFPA and NETA

Building thermography has a small set of standards, each written for one job. Knowing which one a report relies on tells you what its images can and cannot claim.

The short answer

Four standards cover most building thermography in the United States. ASTM C1060 covers qualitative inspection of insulation in frame buildings. ASTM E1186 covers locating air leakage sites, including with a blower door and infrared. ASTM C1153 covers locating wet insulation in low-slope roofs at night. ISO 6781-1 sets requirements for thermographic services in buildings generally. For electrical equipment, NFPA 70B governs maintenance programs in facilities and the ANSI/NETA testing specifications publish the temperature-rise criteria most often quoted. None of them is a home inspection standard, and none is required by New Hampshire's home inspection rules.

ASTM C1060: insulation in frame buildings

C1060 was first approved in 1986 and last revised as C1060-23 in March 2023. Its published scope describes a guide to the proper use of infrared imaging for qualitative thermal inspections of walls, ceilings, roofs and floors of frame buildings, with emphasis on whether insulation is missing or malfunctioning. It states that proof of missing insulation or a malfunctioning envelope requires independent validation, such as visual inspection or in-situ R-value measurement, which is outside the practice. The Snell Group reports that it specifies no direct sun on exterior surfaces for at least three hours before an inspection and no inspection in winds above 15 mph.

Pages on this site that rely on it: missing wall insulation, settled insulation.

ASTM E1186: air leakage sites

E1186, last revised in 2022, sets out practices for locating air leakage sites in building envelopes and air barrier systems. They are qualitative: they find where air leaks, not how much. One practice combines building depressurization or pressurization with infrared scanning, and the standard notes that forced air leakage is required because natural air flows may be too small to locate leaks, and that infrared has the advantage of rapid surveying. Other practices use smoke, theatrical fog, sound and tracer gas.

Pages that rely on it: air leakage at wall tops and ceiling edges, air leakage at windows and doors, and the guide to blower door and infrared testing.

ASTM C1153: wet insulation in roofs

C1153, last revised as C1153-23, applies to infrared imaging at night to locate wet insulation in roofs that have insulation above the deck in contact with the waterproofing. It addresses equipment criteria, weather conditions, roof construction, operator qualifications and verification by invasive test methods, and it does not determine the cause of moisture or its point of entry.

Page that relies on it: wet insulation in a low-slope roof.

ISO 6781-1:2023: thermographic services in buildings

Published in August 2023, ISO 6781-1 is titled Performance of buildings: Detection of heat, air and moisture irregularities in buildings by infrared methods, Part 1: General procedures. It specifies requirements for thermographic services so that users can specify and understand the extent of services, the equipment, the qualifications of equipment operators, image analysts, report authors and those making recommendations, and the reporting of results. It applies to residential, commercial, institutional and special-use buildings. It is the most complete statement of what a thermographic service should include.

NFPA 70B: electrical maintenance

NFPA 70B, the standard for electrical equipment maintenance, changed in its 2023 edition from a recommended practice to a standard. As reported by Teledyne FLIR and TÜV SÜD, it calls for thermographic inspection of electrical equipment in a maintenance program at least every 12 months, and at least every 6 months for equipment in the poorest physical condition category. It is written for facilities with electrical maintenance programs. It does not set requirements for houses.

ANSI/NETA Table 100.18: temperature rise criteria

The InterNational Electrical Testing Association's acceptance and maintenance testing specifications include a table of suggested actions based on temperature rise. As reported by Fluke and training providers, comparing similar components under similar load, a rise of 1 to 3 °C indicates a possible deficiency warranting investigation, 4 to 15 °C a probable deficiency to repair as time permits, and more than 15 °C a major discrepancy to repair immediately. A second column compares components with ambient air. See a hot breaker or connection.

Why the standards matter to a reader

A report that names a standard is making a specific claim. A C1060 finding is a qualitative insulation finding that needs validation. An E1186 survey located leaks but did not measure leakage. A C1153 survey located wet insulation and should include core results. NETA criteria are scales for comparing like components under known load. A report that names no standard is not wrong, but a reader should ask what method it followed.

Where the guidance comes from

ASTM's published summaries of C1060-23, E1186-22 and C1153-23; ISO's listing for ISO 6781-1:2023; Teledyne FLIR on NFPA 70B 2023; Fluke on electrical thermography.

Frequently Asked Questions

Is there a standard for thermal imaging in home inspections?

Not one that New Hampshire requires. The ASTM and ISO standards cover thermographic methods; home inspection standards of practice in New Hampshire do not mention thermal imaging.

What does ASTM C1060 require before calling insulation missing?

Its scope says proof of missing insulation requires independent validation, such as a visual inspection, which is outside the practice.

Does NFPA 70B require my house panel to be scanned?

No. NFPA 70B governs electrical maintenance programs in facilities.

What does a temperature rise of more than 15 °C mean on an electrical component?

Under the NETA criteria, compared with a similar component under similar load, it is a major discrepancy calling for immediate repair.