The short answer
Three specifications matter most for building work. Infrared resolution is the number of temperature-sensing pixels in the detector, such as 160 x 120 or 320 x 240; it is separate from the visible camera's megapixels. Thermal sensitivity, often given as NETD (noise equivalent temperature difference) in millikelvin, is the smallest temperature difference the camera can distinguish. Field of view and the resulting spot size decide how much of a wall each pixel covers at a given distance. Fluke's building inspection guidance suggests at least 120 x 120 pixels and a thermal sensitivity of 100 mK (0.1 °C) or better.
Infrared resolution
A thermal detector is a grid of sensing elements, and each produces one temperature value per pixel. A 160 x 120 detector gives 19,200 measurements per image; a 320 x 240 detector gives 76,800; a 640 x 480 detector gives 307,200. Cameras often upscale or blend the thermal image with a visible photograph, which makes images look sharper on screen without adding thermal data. When comparing cameras, look for the native detector resolution.
Resolution matters most for small or distant targets. A missing stud bay across a room is large and shows on almost any camera. A single overheated terminal in a panel, a narrow air leak at a top plate, or a hot connection on a meter seen from the ground is small, and on a low-resolution camera it may average into the pixels around it and vanish.
Thermal sensitivity
Sensitivity determines whether small temperature differences show as patterns or are lost in noise. Building envelope anomalies are often only a few degrees, and on a marginal day a degree or two. A camera with good sensitivity shows a faint settled-insulation band that a less sensitive camera renders as speckle. The HUD research office, in its overview of thermal imaging for building diagnostics, notes that cameras detect differences of only a few degrees, and that smartphone-based models lack the full capabilities of a high-end camera.
Field of view and spot size
A wide field of view captures a whole wall from close range; a narrow one reaches farther. Each pixel covers a patch of surface that grows with distance. ASTM C1060, the practice for thermographic inspection of insulation, includes measurement spatial resolution among its definitions, and ASTM C1153, the roof moisture practice, addresses instantaneous field of view and field of view as equipment criteria. The practical point: to measure the temperature of something small, get close enough that it fills several pixels.
Other features that matter
Manual level and span. The temperature range the color palette covers. The 2016 edition of the Infraspection Institute's application standards requires that a thermal imaging system used for professional inspections have controls that let the operator adjust the level and gain of the displayed image manually. Auto-ranging can hide subtle patterns or exaggerate trivial ones.
Emissivity and reflected temperature settings. Needed for any temperature reading on surfaces that are not ordinary paint or drywall. See emissivity and reflections.
Radiometric images. A radiometric camera stores a temperature for every pixel, so images can be analyzed later. A non-radiometric image is a picture only.
Visible image pairing. Pairing each thermal image with a visible photo makes reports easier to follow.
Phones and low-cost cameras
Thermal imaging has become cheap. HUD's research office noted in 2019 that camera costs had fallen from over $10,000 to a few hundred dollars. Low-cost cameras and phone attachments can show large patterns, such as a cold attic hatch or a warm radiator, and are useful to an owner. They are less able to show small or subtle anomalies, and their temperature readings are less reliable.
What to ask a thermographer
What is the camera's native infrared resolution and thermal sensitivity? Are the images radiometric? How were level, span and emissivity set? What were the conditions? A thermographer who can answer quickly is likely to have thought about them.
Common mistakes
Comparing megapixels. The visible camera's resolution is irrelevant to thermal detail.
Reading color as temperature. Colors are spread across whatever span the operator chose. A narrow span makes a 1 °F difference look dramatic.
Measuring from too far away. A small target must fill several pixels.
Where the guidance comes from
Fluke's thermal camera checklist, ASTM's published summaries of C1060-23 and C1153-23, and HUD's Thermal Imaging for Building Diagnostics (March 2019).