What the pattern looks like
Most houses in New Hampshire have pitched roofs, but many have a low-slope section: a porch roof, a dormer, a garage, a flat-roofed addition, or a condominium building. On a low-slope roof with insulation laid on the deck under a membrane, wet insulation shows on a night-time thermal image as warm patches against the cooler dry roof. The patches often have defined edges, because water spreads along board joints and stops at seams, and they frequently sit near drains, curbs, penetrations and parapets.
Why wet insulation reads warm at night
The U.S. Department of Energy puts the physics in one line: because wet insulation conducts heat faster than dry insulation, thermographic scans of roofs can often detect roof leaks. On a sunny day the roof absorbs heat. After sunset, dry insulation, which stores little heat, cools quickly; wet insulation, holding water, stores much more and gives it up slowly. For several hours after dark the wet areas stay warmer. Heat from the building below also passes more readily through wet insulation.
What the standard requires
ASTM C1153, last revised as C1153-23 in 2023, is the practice for this survey. Its published scope says it applies to techniques that employ infrared imaging at night to determine the location of wet insulation in roofing systems that have insulation above the deck in contact with the waterproofing. It addresses criteria for the infrared equipment, the weather conditions under which surveys are performed, the effect of roof construction and materials, operator qualifications, and verification of the infrared data by invasive test methods.
It also says what it does not do: it does not provide methods to determine the cause of moisture or its point of entry.
So a C1153 survey answers one question, where the insulation is wet, and expects that answer to be checked by cutting into the roof.
Conditions that make or break the survey
A clear, sunny day to load the roof with heat, followed by a clear, calm evening, gives the strongest contrast. Clouds at night reduce the cooling of dry areas and weaken the contrast. Wind strips heat from the surface. Standing water, ponding, debris and changes in membrane color or ballast all change surface temperature and can mimic or hide wet areas. These are reasons the standard addresses weather and roof conditions specifically.
What else produces warm patches
Extra material. Patches of added membrane, flashing, or thicker insulation hold heat differently.
Ponding and debris. Water and dirt on the surface change how it heats and cools.
Heat from below. A warm room, an uninsulated duct or a skylight under one part of a roof warms that area.
Reflections. Metal flashing and coping have low emissivity and reflect the sky. See emissivity and reflections.
How it is confirmed
The survey marks suspect areas on the roof, usually with paint, and the inspector takes cores or uses moisture probes at marked areas and at dry reference areas. A core shows directly whether the insulation is wet and how deep the water goes. Only then is the wet area outlined for replacement.
Pitched roofs are different
On a shingled pitched roof over a vented attic, the insulation sits on the attic floor, not under the shingles, so a C1153 survey does not apply. Warm patches on a pitched roof mean heat from the house reaching the deck, not wet insulation. See warm roof patches, snowmelt and ice dams.
Common mistakes
Scanning in daylight. The method depends on the night-time cooling curve.
Replacing a roof on the image alone. The standard calls for invasive verification.
Expecting the image to find the leak. It finds wet insulation, which may be some distance from where water entered.
What to do with it
For a building owner, a C1153 survey can turn a full roof replacement into a targeted repair, replacing only wet insulation and fixing the entry points. For a condominium buyer, ask the association whether the roof has been surveyed and when. For a homeowner with a small low-slope section, a roofer's direct inspection is often more practical than a full survey.
Where the guidance comes from
The scope and limits of the practice are from ASTM's published summary of C1153-23. The physics is described by the U.S. Department of Energy in its Energy Saver guidance on thermographic inspections.