What the pattern looks like
The rim joist (also called the band joist) is the board that caps the ends of the floor joists around the perimeter of a house, sitting on the sill plate, which sits on the foundation. From inside an unfinished basement in winter, a thermal camera usually shows the whole rim as a cold band, with colder spots where the sill meets the concrete and where pipes, wires or dryer vents pass through. From the first floor, the same heat loss and air leakage can show as a cold strip along the base of exterior walls or under baseboards.
Why it leaks
The rim is a single thickness of lumber with little to stop air or heat. The joint between the sill and an uneven concrete or stone foundation is often open. The joint between the rim, the sill and the subfloor is another path. In an older New England house with a fieldstone or rubble foundation, the gaps can be large.
In winter the stack effect works on this part of the house in the opposite direction from the attic. Warm air leaving at the top of the house is replaced by cold air drawn in near the bottom, and the rim and sill are the nearest openings. That cold air chills the floor above and can freeze pipes run along an exterior wall in the basement.
Why this is one of the easier findings
Most of the rim joist in an unfinished basement can be seen directly. A thermal image shows which sections are worst, and a flashlight shows the gaps. The image is useful for priorities, not for proof.
What New Hampshire inspectors report
New Hampshire's home inspection standards of practice, in Home 600 of the administrative rules, require the inspector to inspect insulation in unfinished spaces and to report the absence of insulation in unfinished spaces at conditioned surfaces. An uninsulated rim joist in a basement is often reported under that rule, with or without a camera. The standards do not require thermal imaging. See the guide to New Hampshire home inspections and infrared.
What else produces a similar pattern
The top of the foundation wall. Concrete above grade loses heat quickly, so the top of the foundation wall below the rim reads cold too.
A bulkhead or basement door. Basement entries commonly leak and show as a cold area nearby.
Wet concrete. A damp foundation wall reads cooler through evaporation. That is a moisture question, not an air leak. See a cool patch on a ceiling or wall.
How it is confirmed
Look. Check the sill-to-foundation joint for daylight, gaps or missing sealant. Check where pipes and wires pass through. On a windy day, a smoke pencil at the joint shows air movement. A blower door makes the leaks obvious.
Common mistakes
Stuffing fiberglass batts into the rim bays. Fiberglass slows heat but not air, and warm, humid indoor air reaching the cold rim behind a batt can condense. Energy programs commonly use rigid foam sealed at its edges, or spray foam, which control both air and heat.
Sealing combustion air openings. Some older basements rely on leakage for combustion air for a boiler or furnace. An auditor checks combustion appliances when a basement is tightened.
Ignoring insects and decay. A cold, damp rim can hide rot or insect damage. Look at the wood before covering it.
What to do with it
Rim joist sealing and insulation is one of the most common measures in energy audits because it is accessible and the payoff in comfort is direct. For a buyer it is a cost item rather than a defect. For an owner, ask for the rim to be sealed and insulated in the same job as attic air sealing, since both work on the same stack pressure. The blower door and infrared guide describes how audits sequence the work.
Where the guidance comes from
The New Hampshire standards of practice are in the Home 100-700 rules. ASTM's summary of E1186-22 describes infrared air leakage site detection under building depressurization. The U.S. Department of Energy describes blower door and thermographic surveys in its Energy Saver guidance.