The short answer
Each kind of thermal finding has its own confirmation. Moisture is confirmed with a moisture meter at the cool patch and at a dry reference spot. Missing or settled insulation is confirmed by looking into the cavity or measuring in place; ASTM C1060 says proof requires that kind of independent validation. Air leaks are confirmed by comparing images with a blower door running, or by smoke at the joint. Wet roof insulation is confirmed by cores under ASTM C1153. Electrical hot spots are confirmed by an electrician measuring load and checking the connection. A report should say which findings were confirmed and how.
Why images need confirming
A thermal camera measures surface temperature. Many different causes produce the same surface temperature pattern. Fluke's moisture guidance notes that on a cold day moisture and missing insulation can look the same. A cool patch on a ceiling can be wet drywall, a gap in attic insulation, a cold air leak or a supply register. The camera cannot tell them apart. Other tools can.
The standards are built around this. ASTM C1060, the insulation practice, says proof of missing insulation or a malfunctioning envelope requires independent validation. ASTM C1153, the roof moisture practice, includes verification of infrared data using invasive test methods. ASTM E1186, the air leakage practices, lists several detection methods because each has a place.
Moisture
Use a moisture meter. Take a reading in the suspect area and in a nearby area of the same material that reads normal, then compare. The Snell Group's guidance is that the greatest benefit of infrared in moisture work comes from correlating the thermal signature with a meter. The Minnesota Department of Administration's water intrusion guidance says the determination that a material is wet needs a moisture meter. If confirmed, find the source before repairing the surface. See a cool patch on a ceiling or wall and hidden plumbing leaks.
Insulation
Look. Remove a switch plate or receptacle cover with the power off and look into the cavity with a light. Check from the attic or basement where the top or bottom of the cavity is exposed. Where neither works, a small test hole answers the question. For attics, go up and measure depth where the image points. See missing wall insulation and attic insulation gaps.
Air leaks
Compare images before and during building depressurization with a blower door; leaks grow, conduction patterns barely change. Without a blower door, a smoke pencil at the joint on a windy day, or dirty insulation in the attic where air has been filtering through, shows the path. See the guide to blower door and infrared testing.
Electrical
A thermal image of a hot connection is a referral, not a repair order. A licensed electrician measures current, checks torque and looks for damage. New Hampshire's home inspection standards say the inspector shall not measure amperage, voltage or impedance, so that measurement belongs to the electrician. See a hot breaker or connection.
Roofs
On a low-slope roof, mark suspect areas from the night survey and take cores or moisture probe readings at marked areas and at dry references. See wet insulation in a low-slope roof.
Mold
A thermal image cannot find mold. In New Hampshire, paid residential mold assessment requires a national third-party certification under RSA 310-A:189-b. If confirmed moisture raises a mold question, that is a separate service.
What a good report says
For each thermal finding, a good report shows the thermal image and a matching visible photograph, states the conditions (indoor and outdoor temperature, and for electrical findings the load), describes the pattern in plain words, says what confirmation was done and what it found, and recommends what follow-up remains. ISO 6781-1:2023 lists the reporting of results among the things a thermographic service should specify, along with the qualifications of whoever makes recommendations.
Common mistakes
Acting on color alone. Colors depend on the span chosen. Read the scale.
Skipping the dry reference. A meter reading means more beside a reading from the same material that is known to be dry.
Confirming once, in good weather. A roof leak may be dry on a sunny day. A dry reading does not clear a history of leaks.
Opening walls on a hunch. Confirmation first, then demolition.
Where the guidance comes from
ASTM's published summaries of C1060-23, C1153-23 and E1186-22; Fluke's moisture detection application note; The Snell Group's building moisture basics; the Minnesota Department of Administration's infrared water intrusion guidance; and RSA 310-A:189-b.